APS charger is a combination of AP inverter and automatic voltage regulator. While bypassing the input AC to power the loads, the APS pure sine wave inverter also stabilizes the input AC voltage within the range of 230V±10%. Connected with batteries, the APS inverter will run as a UPS with max. transfer time of 10ms.
Features of APS Pure Sine Wave Inverter, Charger, Automatic Voltage Regulator
1.High overload ability of our APS charger is up to 300% rated power(20 sec.), and low voltage trip 9.5V/10V or 10V/10.5V is selectable.
2. APS pure sine wave inverter adopts low quiescent current, and power saver mode to reduce power consumption to 10W(3s sensing cycle)/3W(30s sensing cycle) *. It can extract max. power from various batteries with different protections.
3. The automatic voltage regulator supplies wide stabilizing AC range, and bucking/boosting voltage in 10ms.
4. Our APS pure sine wave inverter can offer 3-step intelligent battery charging, and equipped with 8 preset battery type selector for totally flat batteries. Its powerful charge rate up to 90Amp**. In addition, PFC(power factor correction) is adopted for charger, which has less power consumption than conventional units
5. 10ms typical transfer time between battery and AC, which guarantees power continuity of APS pure sine wave inverter. Its input AC voltage is selectable (184-253V or 154-253V) for different kinds of loads.
6. The APS charger has 15s delay before transfer when AC resumes, and the function of overload protection when it equips with generator. Also, it allows start up and through power with depleted batteries.
7. USB communication port, LCD status display, battery/AC priority switch are available for our APS pure sine wave inverter, it also has 17 alarms/warnings for easier operation and trouble-shooting, and ability to switch the unit on/off. In addition, select/deselect power saver mode can be used too. Note:*For 1KW one. **For some models.
APS Series Inverter & Charger & AVR
Electrical Specifications
Model | APS 1000W | APS 1500W | APS 2000W | APS 3000W | APS 4000W | APS 5000W | APS 6000W | |
Inverter Output | Continuous Output Power | 1000W | 1500W | 2000W | 3000W | 4000W | 5000W | 6000W |
Surge Rating(20s) | 3000W | 4500W | 6000W | 9000W | 12000W | 15000W | 18000W | |
Output Waveform | Pure Sine wave/Same as input(Bypass mode) | |||||||
Nominal Efficiency | >88%(Peak) | |||||||
Line Mode Efficiency | >95% | |||||||
Power Factor | 0.9-1.0 | |||||||
Nominal Output Voltage rms | 100-110-120Vac / 220-230-240Vac | |||||||
Output Voltage Regulation | ±10% RMS | |||||||
Output Frequency | 50Hz ± 0.3Hz/60Hz ± 0.3Hz | |||||||
Short Circuit Protection | Yes( 10s after fault ) | |||||||
Typical transfer Time | 10ms(Max) | |||||||
THD | < 10% | |||||||
DC Input | Nominal Input Voltage | 12.0Vdc | ||||||
( *2 for 24Vdc, *4 for 48Vdc) | ||||||||
Minimum Start Voltage | 10.0Vdc | |||||||
Low Battery Alarm | 10.5Vdc / 11.0Vdc | |||||||
Low Battery Trip | 10.0Vdc / 10.5Vdc | |||||||
High Voltage Alarm | 16.0Vdc | |||||||
Low Battery voltage recover | 15.5Vdc | |||||||
Idle Consumption-Search Mode | < 25 W when Power Saver On | |||||||
Charger | Output Voltage | Depends on battery type | ||||||
Charger Breaker Rating | 10A | 15A | 20A | 20A | 20A | 30A | 30A | |
Max Charge Rate | 35A / 70A | |||||||
Battery Initial Voltage for Start Up | 10-15.7V for 12V( *2 for 24V, *4 for 48V) | |||||||
Over Charge Protection Shutdown | 15.7V for 12V (*2 for 24V, *4 for 48V) | |||||||
Charger curve(4 stage constant current)4 step digital controlled progressive charge | Battery types ( *2 for 24Vdc, *4 for 48Vdc) | |||||||
Remote Control | Yes. Optional | |||||||
Bypass & Protection | Input Voltage Waveform | Sine wave (Grid or Generator) | ||||||
Nominal Voltage | 110Vac | 120Vac | 220Vac | 230Vac | 240Vac | |||
Max Input AC Voltage | 150VAC | 270VAC | ||||||
Nominal Input Frequency | 50Hz or 60Hz (Auto detect) | |||||||
Low Freq Trip | 47±0.3Hz for 50Hz, 57±0.3Hz for 60Hz | |||||||
High Freq Trip | 55±0.3Hz for 50Hz, 65±0.3Hz for 60Hz | |||||||
Overload protection(SMPS load) | Circuit breaker | |||||||
Output Short circuit protection | Circuit breaker | |||||||
Bypass breaker rating | 10A | 15A | 20A | 30A | 30A | 40A | 40A | |
Transfer switch rating | 30amp for UL & TUV | 40amp for UL | ||||||
Bypass without battery connected | Yes | |||||||
Max bypass current | 30amp | 40amp | ||||||
Bypass over load current | 35amp: Alarm | 45amp: Alarm | ||||||
AVR Function | Input AC Voltage Range | 90-140V±4% | 154-253V±4% | |||||
Stabilized Output Voltage rms | 120VAC±10% rms | 230VAC±10% rms | ||||||
Nominal Voltage | 110Vac | 120Vac | 220Vac | 230Vac | 240Vac | |||
(A) Line Low loss N/W (On Battery) | 84/72 | 92/78 | 168/143 | 176/150 | 183/156 | |||
(B) Line Low comeback N/W (On Boost) | 89/77 | 97/83 | 178/153 | 186/160 | 193/166 | |||
(C) Line 2nd boost threshold (On Boost) | ** | ** | ** | ** | ** | |||
(D) Line 2nd boost comeback (On Boost) | ** | ** | ** | ** | ** | |||
(E) Line 1st boost threshold (On Boost) | 99 | 108 | 198 | 207 | 216 | |||
(F) Line 1st boost comeback (On Normal) | 103 | 112 | 205 | 215 | 225 | |||
(G) Line buck comeback (On Normal) | 118 | 128 | 235 | 246 | 256 | |||
(H) Line buck threshold (On Buck) | 121 | 132 | 242 | 253 | 264 | |||
(I) Line high comeback (On Buck) | 127 | 139 | 253 | 266 | 278 | |||
(J) Line high loss (On Battery) | 132 | 144 | 263 | 276 | 288 | |||
Mechanical Specifications | Mounting | Wall mount | ||||||
Inverter Dimensions(L*W*H) | 382*218*179mm | 442*218*179mm | 598*218*179mm | |||||
Inverter Weight | 18KG | 18KG | 20KG | 24KG | 35KG | 45KG | 45KG | |
Shipping Dimensions(L*W*H) | 520*315*300mm | 580*315*300mm | 740*315*300mm | |||||
Shipping Weight | 20KG | 20KG | 22KG | 26KG | 37KG | 47KG | 47KG | |
Display | Status LEDs / Status LEDs+LCD | |||||||
Standard Warranty | 1 Year |